1 Replacement of the Broadcast Tower for KJZZ and KBAQ ADDENDUM NO. 2 RFP # /24/2014 The following clarifications, changes, additions or deletions for this project shall be made to the Contract Documents; all other conditions and work shall remain unchanged. The Addendum supersedes current conditions shown in the Contract Documents. Acknowledge the receipt of these Addenda by inserting its number and date in your bid. This Addendum forms a part of the Contract Documents and modifies them as follows: REMINDER: The first level of RFP response and information is company qualifications only, many of these questions really only come into play for the second phase of the process, when designs actually are started 1. With the pending Holidays and Company shutdowns, would it be possible to extend the bid opening a few days. The response from questions does not provide sufficient time complete the bid process. We will maintain the established timeline. THE INITIAL SUBMITTAL FROM DESIGN BUILD TEAMS IS QUALIFICATIONS ONLY. NO PRICING AND NO DESIGN IS REQUIRED FOR THIS INITIAL SUBMITTAL. 2. Given the existing tower is a small face (24 ) locating the existing KBAQ Directional FM antenna to a larger face will be impossible to duplicate the current pattern and will result in significant modifications and possible need for KBAQ to refile a modified pattern. They must meet the 85% envelope pattern to comply with the FCC License. Would KBAQ consider purchasing a new directional antenna rather than trying to modify the antenna that was designed for the small faced antenna? The current antenna might need to be sent back to the factory for repairs and modifications due to the changes in orientation and face size. Bidder to supply costs for modification of existing antenna as an option to a new replacement antenna modeled for KBAQ. THIS WILL BE PART OF THE PHASE II DESIGN SUBMITTAL AND THEN PART OF THE PHASE III FINAL DESIGN AND COST SUBMITTAL.

2 3. Please provide better quality drawing of the current tower. Exhibit C in not legible. This is a scan of a 1969 blueprint that has been folded in a file for decades. The original print is badly faded. 4. Please confirm which transmission lines are to be provided with the bid and if any should be provided as optional. All transmission lines are to be provided by Bidder. See Exhibit E 5. Please confirm the top and bottom connectors required for each antenna. KJZZ 3 1/8 EIA 6 bolt flanges, top and bottom. KBAQ 3 1/8 EIA 6 bolt Flanges, top and bottom. KJZZ/KBAQ Aux Line and Flanges provided by others. Refer to corrected Exhibit E for other antenna types and connectors. 6. Please confirm the exact type of mounts currently used by each antenna (mount model number or drawing of the mounts required) so that the correct replacement or modifications can be made. Refer to corrected Exhibit E with cut-sheets and equipment manuals provided and/or manufacturer s make and model numbers. For mounts not provided, there are no current records. 7. Please confirm the discrepancies with the transmission line sizes for the FM antennas: a. Will KJZZ be using a 4-1/16 rigid line or a 3-1/8 rigid line or 4 Heliax or 3 Heliax? KJZZ will use 4 1/16 Heliax b. Will KBAQ be using a 3-1/8 rigid line or 3 Heliax? KBAQ will use 3 1/8 Heliax c. Will KJZZ/KBAQ s aux antenna be using a 4-1/16 rigid line or 4 Heliax? KJZZ/KBAQ Aux will use 4 1/16 Heliax to be purchased and installed by others. 8. Please confirm the frequency for the 6 HP dish at Ghz 9. Please confirm if we are to use a Extend Air r5000 (size is 13.5 x 13.5 x 4.5 ) or a 3 diameter dish at 112. If a 3 diameter dish, please confirm if it is to have a radome. Will use customer s existing ExtendAir r5000 with existing 3 ft dish with radome. See Exhibit E 10. Are we to furnish a standoff pole for the future Shively antenna at to 70.3 to mount vertically plumb? Yes.

3 11. Specifications do not specify an inside or outside climbing ladder. If it is inside, at some point there will need to an existing platform which can interfere with FM antenna signal performance. This will be a tower manufacturer design consideration. Customer has no preference. 12. Do you require a steel cable or synthetic cable safety climb device for the entire tower? This will be a tower manufacturer design consideration. Customer has no preference, provided that the safety climb device meets industry standards and OSHA fall protection requirements. 13. Will fencing of the tower be required or supplied by others? No. Site is entirely enclosed inside a secured perimeter fence. 14. Please confirm the Crest Height required for Structure Classification II Exposure C Topographic Category 4. The tower is located on top of Mount Suappoa in Phoenix South Mountain Park. This is a steep hill or mountain. The hill rises about 1300 feet on the north and south sides of the mountain within a 1 to 1 1/2 mile distance. This tower is in a topographic "Category 4" terrain area, based on TIA/222-G, due to the significant uphill slopes on two sides of the mountain at this tower site. 15. Please confirm the center of radiation for the top two FM antennas. Seems to be some conflict between documents. The top antenna shows 193 COR but according to the length, that would put the bottom bay in the aperture of KBAQ s antenna. Since KBAQ is a directional antenna, they typically require more separation between antennas.

4 16. The specifications require driven ground rods to a depth of 30, would they prefer them to be drilled and then filled with a bentonite clay mixture to improve conditions. This is an item for the tower design team to determine the best method based on the Geotech report. 17. On page 19, Section 5.3 of the written specifications, it states that we are responsible for providing and installing the transmission lines. Later in the specifications (pg.31, Section B) we are asked to only install the lines and providing them is not mentioned. Please confirm how and what we are to do. Bidder is to provide specified transmission lines and install all specified transmission lines.

5 18. On page 33, under Section B3 we are asked to make sure that the tower is capable of meeting the specified codes and standards with loadings as described in Section as CaAa loadings. We do not have anything called Section Was this left off the? See Section Antennas and Equipment loading 19. From the documentation provided, it appears that only ERI FM antenna s and transmission line components are to be provided for KJZZ and KBAQ. There appears to be a conflict of interest with ERI being a prime competitor in the bidding process, how will other companies/bidders be competitive when they are forced by default to purchase the equipment from a direct competitor? We do not see any conflict of interest. The successful vendor is to re-install the existing ERI antennas. There are two existing FM's that we are not replacing. We understand that there will be a need for pattern re-modeling of the existing ERI antennas on the ERI test range and that is all the vendor would need to provide with their proposal when the time comes. Other existing antennas will also be re-installed except the aux 4-bay which will be removed by the vendor and ultimately replaced by others with a new 4-bay Shively aux antenna. The list of new antennas that the vendor does need to provide should be provided in the amended Exhibit E. 20. Regarding the location of the new tower. Given the small space and steep grade is it possible to receive a copy of the CAD file that was used supplied as Exhibit B with the original bid documents? This will help in developing the Phase 2 response. The MCCCD KJZZ Tower Site Survey.dwg file is attached 21. In Section B.3 of the bid specifications indicates that the transmission line information shall include their location within or around the tower structure. This indicates that it is acceptable to mount the transmission lines either on the inside or outside of the tower faces. In Section F the specifications state All transmission line shall be mounted to the interior of the tower. Routing of transmission line on the external surface of the towers shall NOT be acceptable. Can you rectify the conflict between these two items? As a point of information a tower that will have only a 54-inch or 48-inch face through the apertures of the FM antennas it is difficult to run large diameter semi-flexible cables inside tower sections this small in size. If it is not feasible to locate transmission lines inside the tower with this face width, we see no problem running the lines outside the tower and making a transition over to the input flange of each antenna. 22. We are basing our tower design on the TIA-222-G parameters for the tower location. Since the tower is located on a ridge we have classified this site as Topographic Category 4. Would MCCCD please specify a Crest Height for the new tower location? Covered in Addendum #2-14

6 23. Section K of the bid specifications seem to indicate that mounts are to be included for each of the antennas relocated to the new tower. Are we correct in assuming that mounts only need to be supplied for antennas initially installed on the tower and that any mounts for future antennas are not to be included? Covered in Addendum #2-6, all mounts and/or mounting pipes to be included for future antennas other than future aux antenna. 24. In bid specification calls for a full height access ladder with climbing prevention on the lower portion. Can you clarify whether a ladder on the outside of the tower is acceptable? The sections of the tower that will support the FM antennas make up a significant portion of the tower and this tower size will be too small to locate a ladder inside the structure. Generally, on structures this size, our practice has been to supply step bolts on all three legs of the tower until the optimized mounting section are reached and these section are climbed using the diagonals and horizontals. A ladder in the aperture of the FM antennas has undesirable effects on the radiated pattern. Are step bolts acceptable in lieu of a ladder? Covered in Addendum # Please confirm if the Design Build team s geotechnical engineer can rely on the subsurface information and laboratory testing data provided in the RAMM Geotechnical Engineering Report for the project or if the Design Build team should hire their own geotechnical engineer to conduct subsurface exploration work. This is the proposing team's call. The firm that provided the geotechnical testing and recommendations is a well-respected, very capable local firm probably known to the proposing firm. The proposing firm is free to contact RAMM to determine their own level of comfort with the information and recommendations made. If they are not comfortable, they ought to propose their own firm to provide their own recommendations during Phase II of the process. In either case, the proposing firm still is obligated to visit, review the site, and provide any questions or discrepancies to us for resolution that they see between the report and their own eyes. This is the same situation that the proposing firm sees on regular building projects- very often the geotechnical report is not part of the contract documents and is provided for information only, with the contractor needing to review the information, draw their own conclusions from it, and provide their own geotech firm if they still are not comfortable. 26. The Design Build team plans to have their own geotechnical engineer prepare a final and site specific geotechnical engineering report for the project. This report will address the design and construction of the preferred foundation alternative for the tower and related structural elements. If this is acceptable, please confirm whether the Design Build

7 geotechnical engineer will be responsible for the Geotechnical Special Inspections during construction related to their alternate design or if the Owner has their own group performing all special inspection services regardless who prepares the report. The District will provide all of the normal testing and observations through an independent third party firm. The consultant/contractor needs to provide any special inspections required by applicable codes to confirm that the work is being installed in accordance with their own engineering drawings and specifications. Either during the Phase II design or certainly by the Phase III final design and pricing, we and the design-build team can create a list of all tests and inspections that will be required and then indicate who will be responsible for what so that final responsibilities and pricing is agreed upon. 27. Please confirm that the Owner will provide a third party engineering or inspection firm to provide the Structural Special Inspections, including all concrete and structural steel related inspections and testing. Any special inspections required to confirm that the work is being installed in accordance with Contract Documents is to be provided by the Design-Build team. Third party testing and inspections will be provided for normal materials testing (backfill, concrete strength, etc.) as well as observations of excavations for foundations. (For example, the District would provide a geotech firm to observe the excavation or drilled holes for a caisson footing or spread footing, but it would be up to the design-build team to provide the special inspection of the rebar placement that it meets the requirements of the Contract Documents, and then a third party testing firm under direct contract to the District would test the concrete for slump and compressive strength). Either during the Phase II design or certainly by the Phase III final design and pricing, we and the design-build team can create a list of all tests and inspections that will be required and then indicate who will be responsible for what so that final responsibilities and pricing is agreed upon. 28. Per section Requires all information submitted to be followed with a signature block and seal of an Arizona Notary. Is an Arizona notary required if submitted from an out of state firm or can the out of state firm acquire the seal of the notary within that state? The out of state firm may use a legal notary from their own state

8 THERE ARE NO FURTHER CHANGES TO THIS ADDENDA END OF ADDENDUM NO. 2 Kelvin Ong Buyer

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement DATE: July 15, 2011 ADDENDUM NUMBER: 2 MODIFYING: Specifications No. 1698 PROJECT: Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement BID TIME AND DATE: 2:00 p.m., July 19, 2011

More information

STANDARDIZED STRUCTURES

STANDARDIZED STRUCTURES Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The

More information

Pole Barns. Why Do I need a Permit? D ID Y OU K N OW? What you need to apply for a building permit: Tips on hiring contractors.

Pole Barns. Why Do I need a Permit? D ID Y OU K N OW? What you need to apply for a building permit: Tips on hiring contractors. Building Guides for Homeowners Pole Barns What you need to apply for a building permit: Site Plan / Footing Detail Page 2 Floor Plan / Truss Details Page 3 Construction Details Pgs 4-5 Permit Application

More information

Invitation to Bid # CC Project Title: High Zone 5.0 Million Gallon Reinforced Concrete Culinary Water Tank Project No.

Invitation to Bid # CC Project Title: High Zone 5.0 Million Gallon Reinforced Concrete Culinary Water Tank Project No. Riverton City Purchasing Department 12830 South 1700 West Riverton, UT 84065 801-208-3175 Fax: 801-254-1810 May 5, 2017 ADDENDUM #3 Invitation to Bid # CC17-332 Project Title: High Zone 5.0 Million Gallon

More information

C o u n t y o f F a i r f a x, V i r g i n i a

C o u n t y o f F a i r f a x, V i r g i n i a 001961 Page 2 C o u n t y o f F a i r f a x, V i r g i n i a A D D E N D U M DATE: August 2, 2016 ADDENDUM NO. 4 TO: REFERENCE: FOR: DUE DATE/TIME: ALL PROSPECTIVE BIDDERS Government Center Generator System

More information

Per your recent request, please find following our quotation for a 140' Sabre Model S3TL self-supporting tower.

Per your recent request, please find following our quotation for a 140' Sabre Model S3TL self-supporting tower. January 27, 2016 DEPARTMENT OF ENTERPRISE SERVICES Attn: Neva Peckham, Procurement Coordinator 1500 Jefferson Street SE Olympia, WA 98504-1411 Dear Ms. Peckham: Per your recent request, please find following

More information

HAWTHORNE AND THAD WATER & WASTEWATER IMPROVEMENTS ITB #124D 16F CITY OF IRVING ADDENDUM # 1 MAY 10, 2016

HAWTHORNE AND THAD WATER & WASTEWATER IMPROVEMENTS ITB #124D 16F CITY OF IRVING ADDENDUM # 1 MAY 10, 2016 HAWTHORNE AND THAD WATER & WASTEWATER IMPROVEMENTS ITB #124D 16F CITY OF IRVING ADDENDUM # 1 MAY 10, 2016 1. THIS ADDENDUM IS HEREBY MADE AS PART OF THIS CONTRACT SPECIFICATION. THIS ADDENDUM IS ISSUED

More information

This Addendum Number One forms part of the Contract Documents and modifies the original Bidding Documents dated June 8, 2016.

This Addendum Number One forms part of the Contract Documents and modifies the original Bidding Documents dated June 8, 2016. ADDENDUM NUMBER ONE - June 15, 2016 CITY OF CLARKSVILLE TO: All Bidders of Record This Addendum Number One forms part of the Contract Documents and modifies the original Bidding Documents dated June 8,

More information

Per your recent request, please find following our quotation for a 140' Sabre Model 2400SRWD guyed tower.

Per your recent request, please find following our quotation for a 140' Sabre Model 2400SRWD guyed tower. January 27, 2016 Attn: Neva Peckham, Procurement Coordinator Dear Ms. Peckham: Per your recent request, please find following our quotation for a 140' Sabre Model 2400SRWD guyed tower. If you have any

More information

2015 MRC Pole Barns. Why Do I need a Permit? D ID Y OU K N OW? What you need to apply for a building permit: Tips on hiring contractors

2015 MRC Pole Barns. Why Do I need a Permit? D ID Y OU K N OW? What you need to apply for a building permit: Tips on hiring contractors Building Guides for Homeowners 2015 MRC Pole Barns What you need to apply for a building permit: Site Plan / Footing Detail Page 2 Floor Plan / Truss Details Page 3 Construction Details Pgs 4-5 Permit

More information

CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS

CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS BID DUE DATE: BID OPENING: ADDENDUM NO. 4 October 4, 2018 October 18, 2018 by 4:00 PM October 19, 2018 at 11:00 AM

More information

Automated Cantilevered Aluminum Sliding Gate

Automated Cantilevered Aluminum Sliding Gate Town of Derry, New Hampshire REQUEST FOR PROPOSALS B18-128 January 25, 2018 The Town of Derry - Department of Public Works is seeking proposals for: Automated Cantilevered Aluminum Sliding Gate Introduction

More information

CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS ADDENDUM NO. 3. September 28, 2018

CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS ADDENDUM NO. 3. September 28, 2018 CITY OF LAREDO, TEXAS AMI COMMUNICATION SYSTEM IMPROVEMENTS-ANTENNA TOWER INSTALLATIONS ADDENDUM NO. 3 September 28, 2018 BID DUE DATE: BID OPENING: October 4, 2018 by 4:00 PM October 5, 2018 at 11:00

More information

INVITATION to BID. 11:00 a.m.

INVITATION to BID. 11:00 a.m. L E G A L N O T I C E INVITATION to BID The Town of Ridgefield invites all interested parties to submit sealed bids on the following: Bid DUE DATE: June 22, 2017 Bid DUE TIME: Bid ITEMS: 11:00 a.m. Aluminum

More information

legend. #1 is a gas relief valve? If so does Enbridge supply with station?

legend. #1 is a gas relief valve? If so does Enbridge supply with station? Michael Pacholok, Director Purchasing and Materials Management Division City Hall, 8 th Floor, West Tower 00 Queen Street West Toronto, Ontario M5H N Joanne Kehoe Manager Construction Services May 4, 06

More information

Installation of Metering System for Monitoring Based Commissioning Program Under Prop. 39 & CCC/IOU

Installation of Metering System for Monitoring Based Commissioning Program Under Prop. 39 & CCC/IOU Installation of Metering System for Monitoring Based Commissioning Program Under Prop. 39 & CCC/IOU PROJECT NO. 1960, RFP NO. 14-15/03 Peralta Community College District 333 East 8th Street, Oakland, CA

More information

Pole Barns. Guides For Homeowners. Why Do I need a Permit? DID YOU KNOW? Charles Abbott Associates. Tips on hiring contractors.

Pole Barns. Guides For Homeowners. Why Do I need a Permit? DID YOU KNOW? Charles Abbott Associates. Tips on hiring contractors. Charles Abbott Associates Pole Barns Guides For Homeowners DID YOU KNOW? No permit is required on structures less than 120 square feet. As owner-builder you are the responsible party of record on such

More information

Rapid Axial Load Testing of Drilled Shafts

Rapid Axial Load Testing of Drilled Shafts Supplemental Technical Specification for Rapid Axial Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 4, 2015 1.0 GENERAL This work shall consist of performing a rapid axial

More information

REQUEST FOR PROPOSAL

REQUEST FOR PROPOSAL September 20, 2016 REQUEST FOR PROPOSAL Design/Build Services for Wood Frame, Metal Siding, Open Front Storage Building for Sewer Department RFP Due October 12, 2016 @ 2:00 pm (local time) BIDDER NAME:

More information

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications.

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications. ADDENDUM NO. 5 ITB-CD-CME-16-10 Southern Well Field Expansion: Equip 5 Wells and New Raw Water Main Phase 2 ISSUE DATE: August 22, 2016 DUE DATE: August 25, 2016 @ 2:00 p.m. SUBJECT: Addendum No. 5 INTENT:

More information

Peralta Community College District th Avenue Oakland, California Phone (510) Fax (510) Purchasing Department

Peralta Community College District th Avenue Oakland, California Phone (510) Fax (510) Purchasing Department Peralta Community College District 501 5 th Avenue Oakland, California 94606 Phone (510) 466-7225 Fax (510) 587-7873 Purchasing Department ADDENDUM No. 2 DATED JULY 2, 2013 TO THE PROJECT MANUAL and PLANS

More information

In case this proposal is accepted by GRDA, the following surety company, or bank, namely,

In case this proposal is accepted by GRDA, the following surety company, or bank, namely, Dollars ($ ) payable to the Grand River Dam Authority, all as called for in the REQUEST FOR PROPOSAL, and it is hereby agreed that in case of failure on the part of the undersigned to execute the Contract

More information

Bi-Directional Static Load Testing of Drilled Shafts

Bi-Directional Static Load Testing of Drilled Shafts Supplemental Technical Specification for Bi-Directional Static Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 2, 2015 1.0 GENERAL This work shall consist of furnishing all

More information

Bi-Directional Static Load Testing of Drilled Shafts

Bi-Directional Static Load Testing of Drilled Shafts Supplemental Technical Specification for Bi-Directional Static Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (01/18) 1.0 GENERAL This work shall consist of furnishing all materials, equipment,

More information

Drainage District(s):

Drainage District(s): APPLICANT: APPLICATION FOR APPROVAL OF CONSTRUCTION ACROSS ESTABLISHED SAC COUNTY DRAINAGE DISTRICTS AND ESTABLISHED MULTI-COUNTY DRAINAGE DISTRICTS Name of Individual or Company Street Address or P. O.

More information

BUREAU Joe Iuviene, AIA January 20, 2017

BUREAU Joe Iuviene, AIA January 20, 2017 architectural BUREAU Joe Iuviene, AIA January 20, 2017 Alterations & Additions NEW TOWN HALL for TOWN OF AUSTERLITZ 816 State Route 203, Spencertown, New York 12165 ADDENDUM NO. 1 This addendum amends

More information

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following: PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral

More information

INSTALLING METEOROLOGICAL MONITORING TOWER AT PROPOSED AND EXISTING NUCLEAR FACILITIES

INSTALLING METEOROLOGICAL MONITORING TOWER AT PROPOSED AND EXISTING NUCLEAR FACILITIES MURRAY AND TRETTEL, INCORPORATED INSTALLING METEOROLOGICAL MONITORING TOWER AT PROPOSED AND EXISTING NUCLEAR FACILITIES Murray and Trettel, Inc. Mark T. Carroll Andrew J. Lotz Heather A. Cramond June 2011

More information

ITEM 555 CHAIN LINK FENCING

ITEM 555 CHAIN LINK FENCING ITEM 555 AFTER MARCH 1, 2012 CHAIN LINK FENCING 555.1 Description. This item shall govern for furnishing the quantities of chain link fencing and gates as shown on the plans, including all posts, bracing

More information

ECMS. home site map help. Project: Municipal / PENNDOT Oversight Non-NHS Construction

ECMS. home site map help. Project: Municipal / PENNDOT Oversight Non-NHS Construction Page 1 of 6 S PECIAL PROVISION home site map help ECMS DOUGLAS GEORGE Project: 30979 Municipal / PENNDOT Oversight Non-NHS Construction Short Description: Pigeon Creek #30 Org Code: 1240 County: Washington

More information

Addendum No. 2. Pre-Bid Meeting Notes and Scope of Work Clarifications

Addendum No. 2. Pre-Bid Meeting Notes and Scope of Work Clarifications Addendum No. 2 Project No. 2016-01EL West Barbour Street 12kV Underground Reconductoring Revisions to Drawings and Specifications Pre-Bid Meeting Notes and Scope of Work Clarifications Replace Section

More information

ADDENDUM No. 2 February 17, Zeeb Road Pathway Scio Township

ADDENDUM No. 2 February 17, Zeeb Road Pathway Scio Township ADDENDUM No. 2 February 17, 2015 Zeeb Road Pathway Scio Township 0159-12-0040 The following changes, additions, and/or clarifications to the Contract Documents shall be incorporated in said documents and

More information

MAINE TURNPIKE AUTHORITY ADDENDUM NO. 2 CONTRACT EXIT 44 SOUTHBOUND ON RAMP IMPROVEMENTS MILE 44.3

MAINE TURNPIKE AUTHORITY ADDENDUM NO. 2 CONTRACT EXIT 44 SOUTHBOUND ON RAMP IMPROVEMENTS MILE 44.3 MAINE TURNPIKE AUTHORITY ADDENDUM NO. 2 CONTRACT 2018.03 EXIT 44 SOUTHBOUND ON RAMP IMPROVEMENTS MILE 44.3 The following changes are made to the Proposal, Specifications, and Plans. PROPOSAL Proposal Sheets

More information

ARROWHEAD LAKES HOMEOWNERS' ASSOCIATION REQUEST FOR NEW OR MODIFICATION OF EXISTING DOCK

ARROWHEAD LAKES HOMEOWNERS' ASSOCIATION REQUEST FOR NEW OR MODIFICATION OF EXISTING DOCK ARROWHEAD LAKES HOMEOWNERS' ASSOCIATION REQUEST FOR NEW OR MODIFICATION OF EXISTING DOCK Phone: 602-674-4372, Fax: 602-870-8231 or email: eodonnell@aamaz.com Owner's Name Phone ( ) Mailing Address City

More information

SECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

SECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following: PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral

More information

00900 ADDENDUM #1. All Document Holders of Record. Date: February 16, Bayfield Waterline Replacement Project

00900 ADDENDUM #1. All Document Holders of Record. Date: February 16, Bayfield Waterline Replacement Project 00900 ADDENDUM #1 Issued to: All Document Holders of Record Date: February 16, 2016 Project: Bayfield Waterline Replacement Project This Addendum forms a part of the Contract described above. The original

More information

SECTION CHAIN LINK FENCES AND GATES (PARK)

SECTION CHAIN LINK FENCES AND GATES (PARK) SECTION 02821 CHAIN LINK FENCES AND GATES (PARK) PART I GENERAL 1.1 SECTION INCLUDES A. Installation of chain link fences, and gate units provided by single source including erection accessories, fittings,

More information

P MWC ADDENDUM # 3 Issue Date: July 5, 2017

P MWC ADDENDUM # 3 Issue Date: July 5, 2017 ADDENDUM OSU and the A&M Systems Purchasing Department ADDENDUM P-88982058-MWC ADDENDUM # 3 Issue Date: July 5, 2017 The Purpose of this Addendum # 3 is to provide Questions and Answers, Contractor Requirement

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

JANUARY 25, 2016 ADDENDUM NO. 3 FOR. ORD Baggage Service Road Retaining Wall Repair

JANUARY 25, 2016 ADDENDUM NO. 3 FOR. ORD Baggage Service Road Retaining Wall Repair JANUARY 25, 2016 ADDENDUM NO. 3 FOR ORD Baggage Service Road Retaining Wall Repair Specifications and Contract Documents Number: 132110 CDA Project Number: H6163.15-02 For which bids are scheduled to be

More information

Enclosed is Addendum No. 1 to SEPTA s Sealed Bid No AKLM Installation (45) Caisson Catenary s and Down Guy Foundations.

Enclosed is Addendum No. 1 to SEPTA s Sealed Bid No AKLM Installation (45) Caisson Catenary s and Down Guy Foundations. January 13, 2017 Dear Sir/Madam: Enclosed is Addendum No. 1 to SEPTA s Sealed Bid No. 16-00282-AKLM Installation (45) Caisson Catenary s and Down Guy Foundations. The bid opening date and time scheduled

More information

CITY OF PUNTA GORDA, FLORIDA

CITY OF PUNTA GORDA, FLORIDA CITY OF PUNTA GORDA, FLORIDA PHONE: (941) 575-3351 FAX: (941) 575-3340 EMAIL: pgpurch@pgorda.us PROCUREMENT DIVISION 326 West Marion Avenue Punta Gorda, Florida, 33950 October 9, 2014 SOLICITATION #F2013124/CONS-PIPEREPL/WWTP

More information

Verizon Wireless Collocation Guidelines Washington/Baltimore/Virginia

Verizon Wireless Collocation Guidelines Washington/Baltimore/Virginia Verizon Wireless Washington/Baltimore/Virginia Network Engineering 1831 Rady Court Richmond, VA 23222 804-347-2572 Verizon Wireless Collocation Guidelines Washington/Baltimore/Virginia The Verizon Wireless

More information

Spring Lake Public Schools. Spring Lake, MI. March RE: High School Storage Buildings

Spring Lake Public Schools. Spring Lake, MI. March RE: High School Storage Buildings Spring Lake Public Schools Spring Lake, MI March 2018 RE: High School Storage Buildings Advertisement for bids Bid Proposal Sealed bids for Spring Lake Public Schools-High School Storage Buildings will

More information

ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14

ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14 September 24, 2014 ADDENDUM #4 Lanier Filter Plant Ozone System Safety Improvements BL079-14 Q1. Please clarify how many submarine doors the perimeter gaskets and gasket hardware must be replaced on. A1.

More information

CITY OF FRIENDSWOOD TECHNICAL SPECIFICATIONS DOCUMENT 00085B ADDENDUM ADDENDUM NO. 1

CITY OF FRIENDSWOOD TECHNICAL SPECIFICATIONS DOCUMENT 00085B ADDENDUM ADDENDUM NO. 1 ADDENDUM Date of Addendum: December 30 th, 2015 PROJECT NAME: Fencing for Sportspark PROJECT NO: GO1507 BID DATE: Tuesday, January 5 th, 2016 FROM: City of Friendswood Department of Public Works 1306 Deepwood

More information

SECTION FIRE HYDRANTS

SECTION FIRE HYDRANTS SECTION 21 11 10 PART 1. GENERAL 1.1 SUMMARY: A. Work consists of furnishing and installing new fire hydrants, (boot with ductile iron retainer gland, standpipe and hydrant complete) plus constructing

More information

of GENERAL. A. Description

of GENERAL. A. Description 02920-1 of 11 SECTION 02920: EARTH TUNNELING 02920.01 GENERAL A. Description Earth tunneling shall include, but not necessarily be limited to, constructing earth tunnels and furnishing and installing tunnel

More information

ADDENDUM NUMBER ONE (1) December 6, The following Addendum shall be incorporated into the Contract Documents for the above referenced project.

ADDENDUM NUMBER ONE (1) December 6, The following Addendum shall be incorporated into the Contract Documents for the above referenced project. TO: ALL HOLDERS OF CONTRACT DOCUMENTS FOR: City of Carlsbad, New Mexico Sanitary Sewer Interceptor 118 Upgrades Phase I Wade M. Chacon P.E. HDR Project Manager/Engineer Bid # 2016-32 ADDENDUM NUMBER ONE

More information

Scaffolding and Raised Platforms

Scaffolding and Raised Platforms Standard Operating Procedures Scaffolding and Raised Platforms Last Modified: JAN 2013 1 of 7 Scaffolding and Raised Platforms I Purpose To provide a guideline for personnel who work around or on stationary

More information

CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE

CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO. 1124 REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE 1 4/13/2016 Questions below pertain to note 4 per drawing, which

More information

Port KC RFP NORTHLAND PARK BUILDING V

Port KC RFP NORTHLAND PARK BUILDING V Port KC RFP NORTHLAND PARK BUILDING V 1. The RFP refers to landscaping plans. However, it does not appear that the landscaping plans were issued with the rest of the RFP. Will these be issued with an addendum?

More information

SEGMENTAL BLOCK RETAINING WALLS. Comply with Division 1 - General Provisions and Covenants, as well as the following:

SEGMENTAL BLOCK RETAINING WALLS. Comply with Division 1 - General Provisions and Covenants, as well as the following: SEGMENTAL BLOCK RETAINING WALLS PART 1 - GENERAL 1.01 SECTION INCLUDES Segmental Block Retaining Walls 1.02 DESCRIPTION OF WORK Constructing segmental block retaining walls. 1.03 SUBMITTALS Comply with

More information

Invitation to Bid MHM

Invitation to Bid MHM Invitation to Bid FENCE @ MHM Responses to an Invitation to Bid will be received by the Purchasing Coordinator, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066 for FENCE @ Merrol

More information

TERMS AND CONDITIONS FORM

TERMS AND CONDITIONS FORM TERMS AND CONDITIONS FORM IMPORTANT : READ ALL THE FOLLOWING TERMS AND CONDITIONS AND SIGN THE ACCEPTANCE CLAUSE FOLLOWING IT 1. The offers through post or hand delivery should be addressed to The Head,

More information

ORDINANCE OF THE NEWTON COUNTY BOARD OF COMMISSIONERS TO REPEAL CONFLICTING PROVISIONS; AND TO AMEND THE ZONING ORDINANCE OF NEWTON COUNTY, GEORGIA

ORDINANCE OF THE NEWTON COUNTY BOARD OF COMMISSIONERS TO REPEAL CONFLICTING PROVISIONS; AND TO AMEND THE ZONING ORDINANCE OF NEWTON COUNTY, GEORGIA ORDINANCE OF THE NEWTON COUNTY BOARD OF COMMISSIONERS TO REPEAL CONFLICTING PROVISIONS; AND TO AMEND THE ZONING ORDINANCE OF NEWTON COUNTY, GEORGIA WHEREAS, the Board of Commissioners of Newton County,

More information

Addendum #2 B14/9830. East Campus Student Life/Business Services/DSR Renovation

Addendum #2 B14/9830. East Campus Student Life/Business Services/DSR Renovation September 25, 2013 Addendum #2 B14/9830 East Campus Student Life/Business Services/DSR Renovation SPECIFICATIONS for East Campus Student Life/Business Services/DSR Renovation Dated: September 5, 2013 This

More information

Regulation 18 August 2009 NO Operations and Maintenance LEVEE ENCROACHMENT STANDARDS AND PROCEDURES

Regulation 18 August 2009 NO Operations and Maintenance LEVEE ENCROACHMENT STANDARDS AND PROCEDURES CENWP-EC DEPARTMENT OF THE ARMY PDR 30-2-5 Portland District, Corps of Engineers (Draft) P.O. Box 2946 Portland, Oregon 97208 Regulation 8 August 2009 NO. 30-2-5 Operations and Maintenance LEVEE ENCROACHMENT

More information

UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04

UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 1. Description This work shall consist of the design, manufacture and construction of a T-WALL structure

More information

March 28, Addendum #4 IFB SA 1713 POTOMAC MILLS T23 WATER TANK REHABILITATION

March 28, Addendum #4 IFB SA 1713 POTOMAC MILLS T23 WATER TANK REHABILITATION Procurement Department P.O. Box 2266 Woodbridge, Virginia 22195-2266 Fax (703) 335-7954 March 28, 2017 Addendum #4 IFB SA 1713 POTOMAC MILLS T23 WATER TANK REHABILITATION THIS SOLICITATION IS HEREBY AMENDED

More information

SECTION LIGHTNING PROTECTION SYSTEM

SECTION LIGHTNING PROTECTION SYSTEM SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

ADDENDUM NO. 1. September 12, 2017 ST. CHARLES COUNTY HEPPERMAN ROAD RECONSTRUCTION

ADDENDUM NO. 1. September 12, 2017 ST. CHARLES COUNTY HEPPERMAN ROAD RECONSTRUCTION ADDENDUM NO. 1 September 12, 2017 ST. CHARLES COUNTY HEPPERMAN ROAD RECONSTRUCTION This Addendum No. 1 modifies original issued bid documents as follows: 1. MODIFICATIONS TO THE PROJECT BID SPECIFICATIONS:

More information

ADDENDUM 2 KODIAK ISLAND BOROUGH CHINIAK TSUNAMI CENTER AND LIBRARY Kodiak, AK

ADDENDUM 2 KODIAK ISLAND BOROUGH CHINIAK TSUNAMI CENTER AND LIBRARY Kodiak, AK ADDENDUM 2 KODIAK ISLAND BOROUGH LIBRARY Kodiak, AK March 7, 2018 TO ALL PLAN HOLDERS OF RECORD: This addendum forms part of and modifies the contract documents as noted below. Bidders must acknowledge

More information

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions.

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions. SECTION 31 23 33 - TRENCHING, BACKFILLING AND COMPACTION PART 1 - GENERAL 1.1 SCOPE A. This Section specifies the requirements for excavating and backfilling for storm sewer, sanitary sewer, water distribution

More information

References. EM , Sections 22 OSHA 29CFR (Subpart L ) UFGS [Latest] ANSI A

References. EM , Sections 22 OSHA 29CFR (Subpart L ) UFGS [Latest] ANSI A References EM385-1-1, Sections 22 OSHA 29CFR 1926.450 (Subpart L ) UFGS-01 35 29[Latest] ANSI A10.8-1988 What Is A Scaffold? An elevated, temporary work platform Three basic types: Supported scaffolds

More information

FLORIDA DEPARTMENT OF TRANSPORTATION

FLORIDA DEPARTMENT OF TRANSPORTATION FLORIDA DEPARTMENT OF TRANSPORTATION ADDENDUM NO. 2 May 12, 2016 RE: ITB#: ITB-DOT-15/16-9049-JP ITB TITLE: Furnish and Install FDOT Tower Replacement: FTE Site x Notice is hereby given of the following

More information

SECTION GROUND WATER STORAGE TANKS

SECTION GROUND WATER STORAGE TANKS SECTION 33 16 13 GROUND WATER STORAGE TANKS PART 1: GENERAL 1.01 SCOPE A. Section includes requirements for designing, fabricating, and erecting a welded steel ground storage tank. 1.02 SYSTEM DESCRIPTION

More information

November 29, CITY OF PLANT CITY Purchasing Division (813)

November 29, CITY OF PLANT CITY Purchasing Division (813) November 29, 2018 CITY OF PLANT CITY Purchasing Division (813) 659-4270 IFB 18-014UM-LG 12-inch Water Transmission Main-Franklin St., Hancock St. and Terrace Drive West ADDENDUM No. 3 *Bidders are required

More information

ADDENDUM No. 1 to BID DOCUMENTS

ADDENDUM No. 1 to BID DOCUMENTS ADDENDUM No. 1 to BID DOCUMENTS For 2018-1 GARDEN APARTMENTS N-2 RECONSTRUCTION PROJECT NY60-2 JANUARY 30, 2018 ADDENDUM No.1 2018-1 GARDEN APARTMENTS N-2 RECONSTRUCTION PROJECT NY60-2 AMSTERDAM HOUSING

More information

CONSTRUCTION SURVEY. Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following:

CONSTRUCTION SURVEY. Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following: CONSTRUCTION SURVEY PART 1 - GENERAL 1.01 SECTION INCLUDES Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following: A. Construction Survey: 1. Project

More information

RFB # ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION

RFB # ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION RFB # 18-0197 ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION The following information was conveyed and discussed

More information

The Town will coordinate with the adjacent property Owner for access allowing work to the East side of the building.

The Town will coordinate with the adjacent property Owner for access allowing work to the East side of the building. ADDENDUM #1 EXTERIOR REPAIRS YOUTH SERVICES BUREAU 63 LINDEN STREET MANCHESTER, CT 06040 BID #15/16-68 S/P+A PROJECT NO. 15.207 DATE: March 15, 2016 The following changes to the Drawings and Project Specifications

More information

Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas

Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas Installation Instructions Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas Bulletin 37835A Revision E Introduction This document specifies typical foundation characteristics, designs,

More information

Grant PUD. Joint Use Standards. For Pole Attachments including: Cable Television Fiber Optics Telecommunications

Grant PUD. Joint Use Standards. For Pole Attachments including: Cable Television Fiber Optics Telecommunications Grant PUD Joint Use Standards For Pole Attachments including: Cable Television Fiber Optics Telecommunications REVISED: July 25, 2018 INTRODUCTION AND OVERVIEW The information contained in these Joint

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION Sheet 1 of 7 KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION NOTE: This special provision is generally written in the imperative mood. The subject, "the

More information

March 3, Addendum No. 1

March 3, Addendum No. 1 March 3, 2017 Addendum No. 1 North Branch Riverwalk: Underbridge Connection at Addison Street from Clark Park to California Park CDOT Project No. E-9-121 Specification No. 133860 For which proposals will

More information

ENGINEERED POWER SOLUTIONS

ENGINEERED POWER SOLUTIONS Date: May 2, 2017 Subject: To: From: Structural Overview of Earth Anchors For PV Ground Mounted Arrays Brian Boguess Nuance Energy Group, Inc. Matthew Gilliss Engineered Power Solutions (EPS) INTRODUCTION

More information

ADDENDUM #1 FOR RFP #PC507 Tree Removal and Sewer/Water Line Rehab at Medical Center PH Community

ADDENDUM #1 FOR RFP #PC507 Tree Removal and Sewer/Water Line Rehab at Medical Center PH Community HOUSING AUTHORITY OF THE COUNTY OF SAN BERNARDINO PROCUREMENT AND CONTRACTS DEPARTMENT 715 E. BRIER DRIVE, SAN BERNARDINO, CA 92408 (909) 890-0644 FAX (909) 890-2349 http://www.hacsb.com/procurement.htm

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION Sheet 1 of 7 NOTE: This special provision is generally written in the imperative mood. The subject, the

More information

SECTION ORNAMENTAL ALUMINUM RAILING

SECTION ORNAMENTAL ALUMINUM RAILING SECTION 05730 ORNAMENTAL ALUMINUM RAILING PART 1 GENERAL 1.1 SECTION INCLUDES A. Aluminum Pipe Railing 1.2 RELATED SECTIONS A. Section 03300 Cast-In-Place Concrete: Placement of sleeves cast in concrete.

More information

ADDENDUM NO. 1 FOR CITY OF CUMMING 900-HP RAW WATER INTAKE PUMP. ADDENDUM DATE: February 10, BID DATE: February 15, 2017, 11:30 a.m.

ADDENDUM NO. 1 FOR CITY OF CUMMING 900-HP RAW WATER INTAKE PUMP. ADDENDUM DATE: February 10, BID DATE: February 15, 2017, 11:30 a.m. ADDENDUM NO. 1 FOR CITY OF CUMMING 900-HP RAW WATER INTAKE PUMP ADDENDUM DATE: February 10, 2017 BID DATE: February 15, 2017, 11:30 a.m. This ADDENDUM is issued to institute the included changes and/or

More information

Sunnyside Valley Irrigation District Enclosed Lateral Improvements Projects Contract Rebid: Region 002A

Sunnyside Valley Irrigation District Enclosed Lateral Improvements Projects Contract Rebid: Region 002A Contract 10-001 Rebid: Region 002A Page 1 of 6 Sunnyside Valley Irrigation District Enclosed Lateral Improvements Projects 2010-2011 Contract 10-001 Rebid: Region 002A ADDENDUM NO. 2 Issued: September

More information

SECTION EXTERIOR ATHLETIC LIGHTING

SECTION EXTERIOR ATHLETIC LIGHTING PART 1 GENERAL 1.1 SECTION INCLUDES A. Sports luminaries and accessories B. Poles 1.2 REFERENCES SECTION 26 58 68 EXTERIOR ATHLETIC LIGHTING A. ANSI C78.379 - Classification of Beam Patterns of Reflector

More information

Addendum No. 3 Glendale Office Addition TMWA Project No Bid No August 25, 2011

Addendum No. 3 Glendale Office Addition TMWA Project No Bid No August 25, 2011 Addendum No. 3 Glendale Office Addition TMWA Project No. 03-017 Bid No. 1112-083 August 25, 2011 The following information, clarifications, changes, and modifications are by reference incorporated into

More information

SPECIAL SPECIFICATION 5787 Manhole Rehabilitation

SPECIAL SPECIFICATION 5787 Manhole Rehabilitation 2004 Specifications CSJ 1062-04-047 SPECIAL SPECIFICATION 5787 Manhole Rehabilitation 1. Description. Repair, rehabilitate, or replace deteriorated, leaking, or structurally unsound existing sanitary sewer

More information

Work Order Number *************************************************************************** SECTION C20 STAIRS 02/18

Work Order Number *************************************************************************** SECTION C20 STAIRS 02/18 NAVFAC PTS-C20 (February 2018) ------------------------------ Preparing Activity: NAVFAC SUPERSEDING PTS-C20 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION C20 STAIRS 02/18 NOTE: This section

More information

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT

CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.MUNI 616 APRIL 2018 CONSTRUCTION SPECIFICATION FOR FOOTINGS AND PADS FOR ELECTRICAL EQUIPMENT TABLE OF CONTENTS 616.01 SCOPE 616.02 REFERENCES 616.03 DEFINITIONS

More information

LEGIS TIVE IMPLEMENTATION GUIDELINES

LEGIS TIVE IMPLEMENTATION GUIDELINES LEGIS TIVE IMPLEMENTATION GUIDELINES HB 2365 WIRELESS FACILITIES; RIGHTS-OF-WAY GUIDE August, 2017 The HB 2365 Guide, published as a service to the members of the League of Arizona Cities and Towns, does

More information

SCAFFOLDS Revision No: 3

SCAFFOLDS Revision No: 3 PAGE 1 OF 6 1.0 PURPOSE/ SCOPE To communicate the safety requirements for the erection, inspection and safe use of scaffolds. Compliance with these requirements will assure employee safety while working

More information

Z Z X X. Installation Instructions Bulletin Revision E Foundation Specifications. For 4.0 Meter Earth Station Antenna

Z Z X X. Installation Instructions Bulletin Revision E Foundation Specifications. For 4.0 Meter Earth Station Antenna Installation Instructions Bulletin 7547321 Revision E Foundation Specifications For 4.0 Meter Earth Station Antenna Y Y Z Z X X ASC Signal Corporation Earth Station Antennas www.ascsignal.com 1 of 18 Copyright

More information

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories. SECTION 02830 CHAIN LINK FENCES AND GATES (GALVANIZED) 1.0 GENERAL 1.1 Section Includes A. Fence framework, fabric, gates, and accessories. B. Excavation for post bases; concrete footing for posts. C.

More information

RUNWAY 34R EXTENSION AND RELATED WORK PACKAGE 2 BRIDGE STRUCTURE EXTENSIONS. Manassas Regional Airport ADDENDUM NO. 2

RUNWAY 34R EXTENSION AND RELATED WORK PACKAGE 2 BRIDGE STRUCTURE EXTENSIONS. Manassas Regional Airport ADDENDUM NO. 2 RUNWAY 34R EXTENSION AND RELATED WORK PACKAGE 2 BRIDGE STRUCTURE EXTENSIONS Manassas Regional Airport ADDENDUM NO. 2 April 19, 2013 This Addendum is hereby made a part of the Contract Documents and Specifications

More information

INVITATION TO BID NUMBER ITB/DA-17/18-36 REBID STORM WATER IMPROVEMENTS AT THE PLANT CITY STATE FARMERS MARKET

INVITATION TO BID NUMBER ITB/DA-17/18-36 REBID STORM WATER IMPROVEMENTS AT THE PLANT CITY STATE FARMERS MARKET ADDENDUM 1 TO: FROM: RE: Vendors Salena Yarbrough INVITATION TO BID NUMBER ITB/DA-17/18-36 REBID STORM WATER IMPROVEMENTS AT THE PLANT CITY STATE FARMERS MARKET This addendum is to provide all potential

More information

SECTION DRILLED CONCRETE PIERS AND SHAFTS

SECTION DRILLED CONCRETE PIERS AND SHAFTS SECTION 31 63 29 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Request for Proposal # Cane Creek Park Fiber Optic Cable Upfit

Request for Proposal # Cane Creek Park Fiber Optic Cable Upfit Request for Proposal # 2018-049 Cane Creek Park Fiber Optic Cable Upfit ADDENDUM NO. 1 ISSUE DATE: February 2, 2018 Bidders on this project are hereby notified that this Addendum shall be attached to and

More information

SPECIAL CONDITIONS FOR HORIZONTAL AUGER BORING (HAB) October, 2006

SPECIAL CONDITIONS FOR HORIZONTAL AUGER BORING (HAB) October, 2006 Michigan Department Of Transportation 3703B (11/06) 1 Materials SPECIAL CONDITIONS FOR HORIZONTAL AUGER BORING (HAB) October, 2006 Page 1 of 5 1.1 Pipe - Pipe used in this method includes an external steel

More information

Applying for a Kinder Morgan Cochin Canada / UTOPIA Canada Proximity & Crossing Permit. Design and Construction Guidelines

Applying for a Kinder Morgan Cochin Canada / UTOPIA Canada Proximity & Crossing Permit. Design and Construction Guidelines Applying for a Kinder Morgan Cochin Canada / UTOPIA Canada Proximity & Crossing Permit Design and Construction Guidelines A Guide to Applying for a Kinder Morgan Cochin Canada / UTOPIA Canada Proximity

More information

STATEMENT OF SPECIAL INSPECTION FORM

STATEMENT OF SPECIAL INSPECTION FORM Project Title: Permit #: Project Address: STATEMENT OF SPECIAL INSPECTION FORM This Statement of Special Inspections is submitted in fulfillment of the requirements of CBC Sections 1704 and 1705. Special

More information

Response: The due date for receipt of proposals has been extended. Please see Amendment

Response: The due date for receipt of proposals has been extended. Please see Amendment 1) Question: Bid Date Due to the complexity, size, and prebid legwork required on a project of this scope, we request that the bid date be extended 45-60days. We appreciate your consideration of this request.

More information