FA R-0014 FTEV , Alter Area for 19 SOS Sim Parts Storage Bldg Questions & Answers

Size: px
Start display at page:

Download "FA R-0014 FTEV , Alter Area for 19 SOS Sim Parts Storage Bldg Questions & Answers"

Transcription

1 FA R-0014 FTEV , Alter Area for 19 SOS Sim Parts Storage Bldg Questions & Answers Question 1 Please clarify the extents of removal of pipe with asbestos containing insulation shown on sheet D-101. At the site visit it was evident the 75 long section of piping shown in the plans at the West end does not exist. Only the North section of pipe remains. However, that section of pipes extends beyond the 135 shown on D-101, actually going into another area of the building through an interior wall drawing M-101 appears to show the existing layout more accurately. So the question is; do we price removing only the existing North section of pipes up-to approximately 135 ft? Or do we include demo of the complete extent of pipes as required per Note 7 on M-101? If it is the latter then we will need actual dimensions of the extent of piping since sheet M-101 does not show all of it. Answer 1 75 portion shown on west wall of D-101 does not exist. Remove only 135 section shown on D-101. Sheets D-101 and M-101 have been revised to reflect the scope of work. Question 2 On Drawing A150, the wall base indicated is 4 while the Specs (096500) Section 2.2 indicates 6. Please verify which height is required. Answer 2 Specifications section updated to reflect 4. Question 3 Answer 3 In Section K of Solicitation on page 24 of 55, it says that the small business size standard is $33,500,000. Should this be $35,500,000? The size standard is actually $36.5M. This will be corrected on the solicitation Question 4 In Sections L and M of solicitation, there are references to Section , paragraphs 1.01 and This section and these paragraphs are not found in the solicitation documents. Is there a section missing?

2 Answer 4 Question 5 Answer 5 Question 6 Answer 6 Question 7 Answer 7 Question 8 Answer 8 Question 9 Answer 9 The reference is incorrect and will be changed to reflect Specification Section The FBO synopsis for this procurement includes the following sentence: Project will be capable of certification under Leadership in Energy and Environmental Design (LEED) for improved building sustainability. Please clarify what the LEED requirements are. Are they only the BD+C requirements described in Section and Section ? Synopsis is for information only and is not a part of the contract documents. Scope of work is contained in design drawings and specifications. The FBO synopsis for this procurement includes the following sentences: Includes minimum DOD force protection standards. Facilities will be designed as permanent construction in accordance with the DOD Unified Facilities Criteria (UFC) , General Building Requirements and UFC , High Performance and Sustainable Building Requirements. This project will comply with DOD anti-terrorism/force protection requirements per UFC Please clarify what the AT/FP requirements are. Synopsis is for information only and is not a part of the contract documents. Scope of work is contained in design drawings and specifications. Please provide as-builts for existing facility. We have some serious concerns about cutting the existing exterior tilt up pre tensioned wall panels for increasing the OH door size. As built drawings reflect the precast panel is a normally reinforced wall. Sheet S-300 Detail 3, New Wall Opening Detail, has been revised to reflect. Provide opening as depicted in detail. The drawings call for Access Controls conduit and boxes to be installed at the new door locations. Will these be required to be connected to an existing system in the building or are raceways all that will be required? Access Control includes only boxes and conduits with pull string running to Rm 100 (Open Office) as stated in Legend on Sheet T-001. There is no connection to existing system. At the site visit we noticed a security camera located in the proposed work area. The drawings do not have any scope listed for Closed Circuit Television. Will there be any CCTV or Security System requirements included in this project? The security camera located in the proposed work area will be removed before the construction contract is awarded. As stated in the Legend on

3 Sheet T-001, the camera (CCTV) scope of work only includes junction boxes and conduit with pull string. There are no other security system requirements. Question 10 Answer 10 Question 11 At the site visit, it was stated that the (2) existing elevated pods would be removed by others prior to this project. These are not noted on the drawings. What (if anything) will be required under this contract for any demo, rework, new construction, etc after these pods are removed by others? Any associated structural, telecom, electrical scopes or other required? Existing equipment and temporary buildings will be removed before contract start. All work is shown on drawings and specifications. B90710 is currently under renovations, please provide the scope of work for this project and/or advise of any facility modifications that may affect this solicitations scope of work. Answer 11 See answer to question 10. Question 12 Answer 12 Question 13 Please advise if there are any known contaminated soils that would require regulated disposal within the construction limits of this solicitation. There are no known contaminated soils. It was noticed during the site visit that the asbestos piping to be removed differed from what was shown on the drawings. Please provide the total LF that the contractor should assume to be abated for this project. Answer 13 See answer to Question 1. Question 14 Answer 14 Question 15 Answer 15 Spec section para TAB Specialist Responsibilities states that the TAB Specialist must participate in the commissioning process. However, there is no commissioning specification provided in the solicitation. Please confirm that HVAC commissioning is not required. Commissioning is not required for this project. Specification (page 8) revised to reflect The solicitation includes the Plastic Laminate Clad Architectural Cabinets spec, please advise what this spec is related to as there doesn't appear to be any cabinetry/casework included in this scope of work. There is no Plastic Laminate Clad Architectural Casework required. Specification Section is not applicable and will be removed from the Contract Documents.

4 Question 16 Please clarify the extents of removal of pipe with asbestos containing insulation shown on sheet D-101. At the site visit it was evident the 75 long section of piping shown in the plans at the West end does not exist. Only the North section of pipe remains. However, that section of pipes extends beyond the 135 shown on D-101, actually going into another area of the building through an interior wall drawing M-101 appears to show the existing layout more accurately. So the question is; do we price removing only the existing North section of pipes up-to approximately 135 ft? Or do we include demo of the complete extent of pipes as required per Note 7 on M-101? If it is the latter then we will need actual dimensions of the extent of piping since sheet M-101 does not show all of it. Answer 16 See Answer to Question 1. Question 17 Sheet A-111 Keynote 15 states that the bollards will be 6 diameter galvanized steel pipe, 6 high, filled with concrete with a rounded concrete top. It also references detail 3/A-502 which shows 4 exposed above ground and 3 below for a total of 7. Sheet A-112 Keynote 10 states 6 high embedded 3 through existing slab/payment for a total of 9. From what I had read in other areas I thought the bollards inside would have a base plate and be bolted down but not according to this statement. Also, Bollard Details 4/S-300 shows 4 exposed above ground with 3 ½ below ground for a total of 7 ½. Please clarify which direction to take with these.. Answer 18 Bollards inside are to be bolted down, per Sheet S-300 Detail 4. Bollards outside are to be embedded below ground. Sheets A-11, A-112, A-502, and A-503 updated to reflect. Question 19 Answer 19 Question 20 Answer 20 Since there is already a fence around the building will we have to construct one for the project also? The existing fence may be utilized to enclose the contractor staging/laydown area. I would like to confirm when the bid bond needs to be submitted. Some notes in the solicitation state the bid bond should be submitted early prior to bid proposal. Normally the bid bond is submitted with the bid proposal. Can you please clarify when the bid bond should be submitted? You can send the bonds any time prior to the proposal due date. For clarification purposes, your bid bond cannot be submitted after the due date/time. You may submit it early or you may submit it with your proposal, but it cannot be submitted late (after proposal due date/time).

5 Question 21 Answer 21 We saw the proposal due date as 07Aug and 08Aug depending on which document we reviewed. Can you please confirm proposal due date and time? The due date on the solicitation is 7 August at I just saw that FBO.gov has 8 August listed. I'm going to change both to 9 August to give enough time to review all of the revisions which will be posted shortly.

Port KC RFP NORTHLAND PARK BUILDING V

Port KC RFP NORTHLAND PARK BUILDING V Port KC RFP NORTHLAND PARK BUILDING V 1. The RFP refers to landscaping plans. However, it does not appear that the landscaping plans were issued with the rest of the RFP. Will these be issued with an addendum?

More information

ProjNet: Logged In User

ProjNet: Logged In User Page 1 of 8 Public / SBU / FOUO Bid Inquiry Contractor Report All Inquiries Project: DDJC Tracy, CA - DLA FY-14 GPW-59 (General Purpose Warehouse) P2# 373676 Review: RFP W91238-14-R-0001 (Ph II due 4-13

More information

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows:

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows: ADDENDUM NO. 1 TO THE DRAWINGS AND SPECIFICATIONS FOR THE New Dishman-McGinnis Elementary School Bowling Green Independent Schools Bowling Green, Kentucky BG 12-256 RTA 1209 March 11, 2013 To All Plan

More information

C o u n t y o f F a i r f a x, V i r g i n i a

C o u n t y o f F a i r f a x, V i r g i n i a 001961 Page 2 C o u n t y o f F a i r f a x, V i r g i n i a A D D E N D U M DATE: August 2, 2016 ADDENDUM NO. 4 TO: REFERENCE: FOR: DUE DATE/TIME: ALL PROSPECTIVE BIDDERS Government Center Generator System

More information

The PPI log is for informational purposes only. It does not amend the RFP. If a revision to the RFP is required, a formal amendment will be issued.

The PPI log is for informational purposes only. It does not amend the RFP. If a revision to the RFP is required, a formal amendment will be issued. 69450-15-R-1090 (/) 1 2-Mar-15 Page 16, Paragraph (2) The solicitation states that the JV prime has one relevant project or each member of the JV has relevant experience. Do you mean either party not both?

More information

Addendum No. 3 pg. 1. Project: Prolift Project No.: Subject: Addendum No. 3 Date: Monday, July 18, 2016

Addendum No. 3 pg. 1. Project: Prolift Project No.: Subject: Addendum No. 3 Date: Monday, July 18, 2016 Addendum No. 3 pg. 1 Project: Prolift Project No.: 201613.01 Subject: Addendum No. 3 Date: Monday, July 18, 2016 This addendum is a part of the bid documents. Acknowledge receipt on the proposal form.

More information

ADDENDUM No. 1. H.S. Thompson Elementary School Abatement Org #307

ADDENDUM No. 1. H.S. Thompson Elementary School Abatement Org #307 ADDENDUM No. 1 for BP# 301A H.S. Thompson Elementary School Abatement Org #307 DALLAS INDEPENDENT SCHOOL DISTRICT December 01, 2017 Any addendum issued will be listed or posted at the Bond Program website

More information

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 QUESTIONS & ANSWERS FOR B1900051 SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 Answers to questions: 1) Question: Is the existing slab post tensioned? Answer: No. Existing slab is 4 thick with welded

More information

Understanding Consultants Needed for Your Building Project By Amy Green, Owner, Architect, Interior Designer & LEED AP of amy green design 579 W

Understanding Consultants Needed for Your Building Project By Amy Green, Owner, Architect, Interior Designer & LEED AP of amy green design 579 W Understanding Consultants Needed for Your Building Project By Amy Green, Owner, Architect, Interior Designer & LEED AP of amy green design 579 W 177th St. #51, NYC, NY 10033 amy@amygreendesign.com 503.438.5411

More information

Division 00 Procurement and Contracting Requirements

Division 00 Procurement and Contracting Requirements SECTION 00 01 10 TABLE OF CONTENTS Division SECTION NO. VOLUME ONE Title SECTION TITLE Division 00 Procurement and Contracting Requirements 00 11 00 Invitation to Bidders 00 21 00 Instructions to Bidders

More information

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport RESPONSES TO QUESTIONS and/or RFI s Date: 6/1/2018 The attention of Contractors submitting Filed Sub-Bids

More information

TABLE OF CONTENTS Structural Library

TABLE OF CONTENTS Structural Library Title Description DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 000101 Project Title Page Project Manual title page. 000107 Seals Page For seals of design professionals on Project Manual. 000115

More information

Solicitation Number: FA B-A001 Project Numbers: RKMF Demo Base Gymnasium & RKMF Demo Pool Facilities.

Solicitation Number: FA B-A001 Project Numbers: RKMF Demo Base Gymnasium & RKMF Demo Pool Facilities. Solicitation Number: FA4861-14-B-A001 Project Numbers: RKMF 13-0134 Demo Base Gymnasium & RKMF 130135 Demo Pool Facilities Responses to RFIs 1. Does all the building material get hauled off base? Response:

More information

ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT WEST VALLEY COLLEGE

ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT WEST VALLEY COLLEGE ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT AT WEST VALLEY COLLEGE Owner West Valley-Mission Community College District Saratoga, California Bid #01-1516 12-22-15 WEST VALLEY-MISSION

More information

City of St. Petersburg

City of St. Petersburg Page 1 of 5 QUESTIONS AND RESPONSES City of St. Petersburg IFB 7395 Lift Station 85 Albert Whitted Master 30 Force Main Part D Project No. 12013-411 November 29, 2012 Responses to Questions: Q1 R1 Q2 R2

More information

J~e~~r Senior Director of Construction Services Facilities Design and Construction UNIVERSITY OF CALIFORNIA, SAN DIEGO.

J~e~~r Senior Director of Construction Services Facilities Design and Construction UNIVERSITY OF CALIFORNIA, SAN DIEGO. BERKELEY DAVIS IR VINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SAN!' A BARBARA SANT A CRUZ OFFICE OF THE ASSIST ANT VICE CHANCELLOR CAMPUS ARCHITECT - FACILITIES DESIGN & CONSTRUCTION TEL:

More information

The PPI log is for informational purposes only. It does not amend the RFP. If a revision to the RFP is required, a formal amendment will be issued.

The PPI log is for informational purposes only. It does not amend the RFP. If a revision to the RFP is required, a formal amendment will be issued. 69450-15-R-1090 (Y/) 1 2-Mar-15 Page 16, Paragraph (2) The solicitation states that the JV prime has one relevant project or each member of the JV has relevant experience. Do you mean either party not

More information

CHARLES COUNTY GOVERNMENT ITB NO GOVERNMENT BUILDING ATRIUM RENOVATION

CHARLES COUNTY GOVERNMENT ITB NO GOVERNMENT BUILDING ATRIUM RENOVATION CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 July 26, 2017 ITB NO. 18-03 GOVERNMENT BUILDING ATRIUM RENOVATION ADDENDUM NUMBER

More information

ADDENDUM #2 REQUEST FOR COMPETITIVE SEALED PROPOSALS FOR A GENERAL CONTRACTOR. The University of Texas Health Science Center at San Antonio

ADDENDUM #2 REQUEST FOR COMPETITIVE SEALED PROPOSALS FOR A GENERAL CONTRACTOR. The University of Texas Health Science Center at San Antonio ADDENDUM #2 REQUEST FOR COMPETITIVE SEALED PROPOSALS FOR A GENERAL CONTRACTOR The University of Texas Health Science Center at San Antonio Renovate Floor 1 and Floor 2 of the PARC Bldg. RFP No.: 745-16-9935

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS USACE / NAVFAC / AFCEC / NASA UFGS-00 22 13.00 20 (February 2014) Change 2-05/16 ----------------------------------- Preparing Activity: NAVFAC Superseding UFGS-00 22 13 (May 2011) UNIFIED FACILITIES GUIDE

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated.

This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated. BIDDER RESPONSES RIARNG P-6 ADDITION TO ALL BIDDERS OF RECORD: This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated. ADDENDUM 001 2/14/2019

More information

186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT

186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT 186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS PROJECT NUMBER MDVL092051 Renovate Vehicle Maintenance Facility Bldg 200 23 June 2017 ADDENDUM #1 PERFORMANCE WORK STATEMENT 1.0 SCOPE. This addendum to

More information

REBECCA LG BOSTICK, ARCHITECTS, INC

REBECCA LG BOSTICK, ARCHITECTS, INC REBECCA LG BOSTICK, ARCHITECTS, INC 703-768-2250 ADDENDUM NO. 3 Page 1 of 4 (plus attachments -2 pages) SILVERBROOK ELEMENTARY SCHOOL RENOVATION Fairfax County Public Schools 9350 Crosspointe Drive, Fairfax

More information

1 data PIC location (with 2 ports) typically asf for multiple staff members

1 data PIC location (with 2 ports) typically asf for multiple staff members 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

legend. #1 is a gas relief valve? If so does Enbridge supply with station?

legend. #1 is a gas relief valve? If so does Enbridge supply with station? Michael Pacholok, Director Purchasing and Materials Management Division City Hall, 8 th Floor, West Tower 00 Queen Street West Toronto, Ontario M5H N Joanne Kehoe Manager Construction Services May 4, 06

More information

Response: The due date for receipt of proposals has been extended. Please see Amendment

Response: The due date for receipt of proposals has been extended. Please see Amendment 1) Question: Bid Date Due to the complexity, size, and prebid legwork required on a project of this scope, we request that the bid date be extended 45-60days. We appreciate your consideration of this request.

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

AMENDMENT OF SOLICITATION

AMENDMENT OF SOLICITATION Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION PAGE 1 Metropolitan Washington Airports Authority 1A. AMENDMENT OF SOLICITATION NO. 1B. DATED Procurement

More information

PURCHASING DEPARTMENT

PURCHASING DEPARTMENT PURCHASING DEPARTMENT The bid listed below has had addenda issued. Documents are available over the Internet at http://www.norwalkct.org Adobe Acrobat reader is required to view this document. If you do

More information

TABLE OF CONTENTS VOLUME 1. DIVISION 00 - INTRODUCTORY INFORMATION, BIDDING REQUIREMENTS, CONTRACT FORMS & CONDITIONS OF THE CONTRACT Pages

TABLE OF CONTENTS VOLUME 1. DIVISION 00 - INTRODUCTORY INFORMATION, BIDDING REQUIREMENTS, CONTRACT FORMS & CONDITIONS OF THE CONTRACT Pages TABLE OF CONTENTS VOLUME 1 DIVISION 00 - INTRODUCTORY INFORMATION, BIDDING REQUIREMENTS, CONTRACT FORMS & CONDITIONS OF THE CONTRACT Pages SCHEDULE OF DRAWINGS...... 1 PROJECT PERSONNEL & DIRECTORY......

More information

Energy Transfer Station Installation Only, Carleton to Sexton District Energy

Energy Transfer Station Installation Only, Carleton to Sexton District Energy ADDENDUM FORM INVITATION TO TENDER: #2015-021 ADDENDUM NO: 1 DATE ISSUED: February 23, 2015 ISSUED BY: Mike Drane DESCRIPTION: INSTRUCTIONS: Energy Transfer Station Installation Only, Carleton to Sexton

More information

ADDENDUM #9 DATE: 1/12/17 TO:

ADDENDUM #9 DATE: 1/12/17 TO: ADDENDUM #9 DATE: 1/12/17 TO: Vince O Brien (Anne Arundel County Public Schools) FROM: Andy Locke (Jacobs Engineering) RE: Arnold Elementary School Replacement, All Bid Packages ADDENDUM #9: Revisions

More information

Via Internet Posting 14 pages

Via Internet Posting 14 pages Michael Pacholok Director Purchasing and Materials Management Division City Hall, 18 th Floor, West Tower 100 Queen Street West Toronto, Ontario M5H 2N2 Joanne Kehoe Manager Construction Services March

More information

RFP /ME - ADDENDUM 2

RFP /ME - ADDENDUM 2 RFP 201013/ME - ADDENDUM 2 RFP Closing: February 5, 2015 at 2:00 PM (Local Time) Page 1 of 33 RFP Number: 201013/ME Date: January 28, 2015 RETURN PROPOSALS AS SHOWN BELOW Copies of proposal required: Eight

More information

BID ADDENDUM #1 September 24, 2010

BID ADDENDUM #1 September 24, 2010 BID ADDENDUM #1 September 24, 2010 To: Prospective Bidders/Planholders For: Science 1 Seismic Retrofit & Renovation California State University Stanislaus One University Circle, Turlock, CA 95382 Bid /

More information

December 2, Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC).

December 2, Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC). December 2, 2016 Dear Sir/Madam Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No. 16-00249-AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC). The bid opening date and time scheduled for Wednesday,

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

STATE OF NEW HAMPSHIRE DEPARTMENT OF NATURAL AND CULTURAL RESOURCES DIVISION OF PARKS AND RECREATION SKI PATROL HUT PROJECT #: CAP 1804

STATE OF NEW HAMPSHIRE DEPARTMENT OF NATURAL AND CULTURAL RESOURCES DIVISION OF PARKS AND RECREATION SKI PATROL HUT PROJECT #: CAP 1804 STATE OF NEW HAMPSHIRE DEPARTMENT OF NATURAL AND CULTURAL RESOURCES DIVISION OF PARKS AND RECREATION PROJECT #: CAP 1804 FRANCONIA NOTCH STATE PARK FRANCONIA, NEW HAMPSHIRE BID SET 8/4/2017 DRAWING LIST:

More information

Requests for Information pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 2018

Requests for Information pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 2018 Requests for Information - 05.0.1 5pm Draft for Request for Proposals Sprouts - Shell/Civil Issued on April 25, 201 RFI 01 Is the RFP due at 4pm or 5pm on May 16th? Response: RFI 02 Do you have an anticipated

More information

Division 03 - Concrete Section New Westminister Multi-Use Civic Facility & Office Building Project No Page 1

Division 03 - Concrete Section New Westminister Multi-Use Civic Facility & Office Building Project No Page 1 Project No. 210022 Page 1 PART 1 GENERAL 1.7 Documents.1 The General Conditions of the Canadian Standard Construction Document CCDC-2, together with all amendments and supplements and Division 1 General

More information

ADDENDUM # 1 To: File RFP for: New Affordable Home Construction Services

ADDENDUM # 1 To: File RFP for: New Affordable Home Construction Services Procurement Department ADDENDUM # 1 To: File 1605-909-23-4532 RFP for: New Affordable Home Construction Services Please note the following change: Change #1 RFP closing date and time is changed to July

More information

ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION THE TOWN OF MALTA AND A PORTION OF THE 115KV

ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION THE TOWN OF MALTA AND A PORTION OF THE 115KV ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION IN THE TOWN OF MALTA AND A PORTION OF THE 115KV LUTHER FOREST STATION IN THE TOWN OF STILLWATER SARATOGA

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Issued for Bid West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS

Issued for Bid West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS 669.7403.001 West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS Page C-111 Advertisement for Bids 1-2 C-200 Instruction to Bidders 1-10 C-410 Bid Form for Construction Projects

More information

Section 7: Specifications

Section 7: Specifications Section 7: Specifications 29 31 Building Boundary of Clear Area See Note # 1 8' Shrubs 8' Concrete Pad Equipment 8' TRAVELED WAY M Meter Pedestal 8' Curb Protective Vehicle Posts (Bollards) If Required

More information

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

ADDENDUM 3 TO INVITATION FOR BID 5300-FG. Interior Renovations for UNLV Quality Assurance Lab (QAL) and UNLV Monitoring Systems Lab (MSL)

ADDENDUM 3 TO INVITATION FOR BID 5300-FG. Interior Renovations for UNLV Quality Assurance Lab (QAL) and UNLV Monitoring Systems Lab (MSL) ADDENDUM 3 TO INVITATION FOR BID 5300-FG Interior Renovations for UNLV Quality Assurance Lab (QAL) and UNLV Monitoring Systems Lab (MSL) University of Nevada, Las Vegas Purchasing Department 4505 Maryland

More information

Project Manual Index of Specifications Shenandoah Schools Concession Building

Project Manual Index of Specifications Shenandoah Schools Concession Building INDEX OF SPECIFICATIONS Division 0..BIDDING AND CONTRACT REQUIREMENTS 00 11 13 Advertisement for Bids 00 21 13 Instructions to Bidders 00 41 00 Bid Forms 00 43 13 Bid Security Form 00 72 00 General Conditions

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

DATE: July 27, 2018 TO: All Bidders FROM: Jo Nell Miller, Purchasing Specialist SUBJECT: Addendum 2 Bid 550 Moorpark College Gymnasium Renovation

DATE: July 27, 2018 TO: All Bidders FROM: Jo Nell Miller, Purchasing Specialist SUBJECT: Addendum 2 Bid 550 Moorpark College Gymnasium Renovation DATE: July 27, 2018 TO: All Bidders FROM: Jo Nell Miller, Purchasing Specialist SUBJECT: Addendum 2 Bid 550 Moorpark College Gymnasium Renovation This addendum is hereby made part of the Contract Documents

More information

FABRICATED FIREPROOFED STEEL COLUMNS

FABRICATED FIREPROOFED STEEL COLUMNS BLACK ROCK FIREPROOF COLUMN Black Rock Fireproof Column Co. 164 School Street East Hartford, CT 06108 Phone: (860) 936-3344 Fax: (860) 289-2908 Email: info@blackrockcolumn.com Website: www.blackrockfireproof.com

More information

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT Effective September 6, 2018, Addendum No. 3 (THREE), {Pages 1-7 and the applicable attachment(s)}, is associated

More information

September 23, 2016 ADDENDUM #2

September 23, 2016 ADDENDUM #2 September 23, 2016 ADDENDUM #2 To: From: Subject: Prospective Bidders St. Johns County Purchasing Department Bid No. 16-55 St. Johns County Building Services Renovation & Remodeling. This Addendum #2 is

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION / SLAB AND SITE WORK

INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION / SLAB AND SITE WORK ADDENDUM 3 TO: FROM: RE: Vendors Christie Hutchinson, Purchasing Director INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION

More information

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows:

A. Hazardous Areas: Hazardous areas as defined by the NEC as Class I, Division 1, Group D, or Class I, Division 2, Group D hazardous are as follows: SECTION 16050 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: General requirements for providing basic electrical materials and methods. B. Related Work Specified in Other Sections Includes: 1. Certain

More information

SECTION FACILITY LIGHTNING PROTECTION

SECTION FACILITY LIGHTNING PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable

More information

EXHIBIT C GUARANTEED MAXIMUM PRICE TO THE CONTINUING CONTRACT FOR CONSTRUCTION MANAGEMENT SERVICES/RFQ #14-Q-009-KR BY AND BETWEEN

EXHIBIT C GUARANTEED MAXIMUM PRICE TO THE CONTINUING CONTRACT FOR CONSTRUCTION MANAGEMENT SERVICES/RFQ #14-Q-009-KR BY AND BETWEEN EXHIBIT C GUARANTEED MAXIMUM PRICE TO THE CONTINUING CONTRACT FOR CONSTRUCTION MANAGEMENT SERVICES/RFQ #14-Q-009-KR BY AND BETWEEN THE SCHOOL BOARD OF BREVARD COUNTY, FLORIDA 2700 Judge Fran Jamieson Way

More information

South Londonderry Township Pre-Bid Meeting Minutes. August 24, 2016

South Londonderry Township Pre-Bid Meeting Minutes. August 24, 2016 Beers + Hoffman Scott L. Shonk, R.A., AIA, LEED AP Peter D. Kerekgyarto, R.A., AIA, LEED AP Timothy M. Schwear, Assoc. AIA C. Bruce Christman Jr., AIA, LEED AP, GAC Robert P. Hoffman, R.A., AIA South Londonderry

More information

Refer to Sheet A-203 and modify Floor Plan Demolition Keynote #23 as follows:

Refer to Sheet A-203 and modify Floor Plan Demolition Keynote #23 as follows: 10 September 2018 ADDENDUM NUMBER 2 To the Contract Documents for the Construction of Locker Room Modernization @ Corona High School (Bid No. 17/18-008) (DSA A#04-116960) Corona-Norco Unified School District

More information

HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District

HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District Facilities and School Safety Committee Meeting October 25, 2018 Progress Update PROGRESS UPDATE Rien Construction (General

More information

SECTION GENERAL REQUIREMENTS PART 1 - GENERAL I 1 GENERAL REQUIRMENTS

SECTION GENERAL REQUIREMENTS PART 1 - GENERAL I 1 GENERAL REQUIRMENTS SECTION 01 00 00 GENERAL REQUIREMENTS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Summary of Work: 1. General 2. Contract. B. Contract Considerations: 1. Schedule of values. 2. Applications for payment. 3.

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

REQUEST FOR COMPETITIVE SEALED PROPOSAL PROJECT NO. CSP CULINARY ARTS CENTER QUESTIONS AND ANSWERS NO. 1

REQUEST FOR COMPETITIVE SEALED PROPOSAL PROJECT NO. CSP CULINARY ARTS CENTER QUESTIONS AND ANSWERS NO. 1 REQUEST FOR COMPETITIVE SEALED PROPOSAL PROJECT NO. CSP 17-31 CULINARY ARTS CENTER QUESTIONS AND ANSWERS NO. 1 Date: January 24, 2017 To: From: Prospective Respondents Procurement Operations Department,

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION MULTIPLE CONTRACT SUMMARY

2016 CDM Smith All Rights Reserved July 2016 SECTION MULTIPLE CONTRACT SUMMARY PART 1 - GENERAL SECTION 01 01 11 MULTIPLE CONTRACT SUMMARY 1.01 SCOPE OF WORK A. This Section includes a summary of each Contract, including responsibilities for coordination and temporary facilities

More information

HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District

HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District HILLVIEW ELEMENTARY ADDITIONS AND ALTERATIONS Grove City Area School District Facilities and School Safety Committee Meeting September 20, 2018 Progress Update PROGRESS UPDATE Rien Construction (General

More information

Completed. Project. Melbourne High School. Comprehensive Additions and Renovations

Completed. Project. Melbourne High School. Comprehensive Additions and Renovations Project Update Project Update September 8, 2006 January 06, 2010 Project Manager Project Manager Anibal Caussade Dennis Bonny Field Coordinator Field Coordinator Bud Ball Paul Friel Project Budget Project

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

Subject: Consultation regarding proposed Posey Tube Rehabilitation.

Subject: Consultation regarding proposed Posey Tube Rehabilitation. STATE OF CALIFORNIA-------BUSINESS. TRANSPORTATION AND HOUSING AGENCY DEPARTMENT OF TRANSPORTATION Office of Cultural Resource Studies, Mail Station 8-A P. 0. Box 23660 Oakland, CA 94623-0660 Phone (510)

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

Demolition Process Flow

Demolition Process Flow Demolition A to Z Demolition Demolition Process Flow Property identified for demolition Asbestos Survey Does the property need asbestos abatement? If, yes Asbestos abatement contractor selected Work order

More information

SECTION 11 Architectural and Nonstructural Elements Field Investigation

SECTION 11 Architectural and Nonstructural Elements Field Investigation SECTION 11 Architectural and Nonstructural Elements Field Investigation Types of Data to Be Collected and Recorded Research in these fields should be directed at determining the effect that architecture

More information

METRO RESPONSE TO PROSPECTIVE BIDDERS QUESTIONS

METRO RESPONSE TO PROSPECTIVE BIDDERS QUESTIONS METRO RESPONSE TO PROSPECTIVE BIDDERS QUESTIONS Wednesday, October 31, 2018 Solicitation No. 4018000193 ROC / Redline Tie Replacement, Drainage & Subgrade Improvements 1. Will the Thickness of Sub ballast

More information

SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida Telephone Fax

SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida Telephone Fax SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida 34236 Telephone 941-861-5266 Fax 941-861-5129 ADDENDUM NO.1 BID # : #153025CS CCSWDC Leachate Lift Station Rehabilitation

More information

SECTION ADDENDUM NUMBER ONE

SECTION ADDENDUM NUMBER ONE Softball Field Repairs and Upgrades 03 February 2012 University of South Carolina Upstate State Project Number: H34-I350 DP3 Architects Project Number: 11124 GENERAL INFORMATION SECTION 00 09 10 ADDENDUM

More information

Notice: Request for Proposals. RFP Question & Answers #1-35

Notice: Request for Proposals. RFP Question & Answers #1-35 Notice: Request for Proposals for Construction Manager At Risk RFP Question & Answers #1-35 Publication of Proposal December 31, 2012 Submission of Proposal Deadline January 28, 2013 workforceconnections

More information

JMU Capital Projects SWaM Outreach Event Presentations

JMU Capital Projects SWaM Outreach Event Presentations JMU Capital Projects SWaM Outreach Event Presentations Kjellstrom + Lee Contact: Jessica Marcus jmarcus@kjellstromandlee.com Project: College of Business Renovation/Expansion Please contact Kjellstrom

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

DIVISION 5 METALS SECTION STRUCTURAL STEEL

DIVISION 5 METALS SECTION STRUCTURAL STEEL DIVISION 5 METALS SECTION 05 12 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: All labor and materials required to furnish and install the structural steel shown on the Drawings and required by these

More information

CLARION UNIVERSITY OF PENNSYLVANIA STATE SYSTEM OF HIGHER EDUCATION ISSUE DATE: September 4, 2014

CLARION UNIVERSITY OF PENNSYLVANIA STATE SYSTEM OF HIGHER EDUCATION ISSUE DATE: September 4, 2014 CLARION UNIVERSITY OF PENNSYLVANIA STATE SYSTEM OF HIGHER EDUCATION ISSUE DATE: September 4, 2014 PROJECT NO: PROJECT NAME: BIDS DUE: 2:00 P.M., EST., September 24, 2014 ADDENDUM NO. 3 TO: Prospective

More information

Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification No.

Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification No. Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification 1 01 Allow any alternative design for composite beam and slab for the structural

More information

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS ARCHITECTURE, LLC 1827 1 ST AVENUE NORTH, SUITE 104 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 3 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

ADDENDUM 1 August 28, Construction & Facility Management Office 1636 Gold Star Drive Raleigh, NC 27607

ADDENDUM 1 August 28, Construction & Facility Management Office 1636 Gold Star Drive Raleigh, NC 27607 Nashville Readiness Center Building Renovation Smith Sinnett / 2013024 North Carolina National Guard SCO ID#: 130999902-E ADDENDUM 1 August 28, 2017 NASHVILLE READINESS CENTER BUILDING RENOVATION SCO#:

More information

Minneapolis Community and Technical College T-Building Floor 2 Student Affairs Cost Estimating Form Templates - Exhibit C

Minneapolis Community and Technical College T-Building Floor 2 Student Affairs Cost Estimating Form Templates - Exhibit C 2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 9 20 2 22 23 24 25 26 27 28 29 30 3 32 33 34 35 36 37 38 39 40 4 42 43 44 45 46 DIVISION 02 EXISTING CONDITIONS Demolition; Removal & Disposal: CMU Partitions AD Quan UM

More information

PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE

PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE PROJECT MANUAL FOR: HUMPHREYS CO. SHERRILL BUILDING RENOVATIONS: NEW URGENT CARE CLINIC & EXTENSION SERVICE OFFICE HUMPHREYS COUNTY BOARD OF SUPERVISOR BELZONI, MISSISSIPPI APRIL 20, 2016 EMILY POOLE ARCHITECTURE,

More information

PMCE Emergency Department Shell Fit-Out

PMCE Emergency Department Shell Fit-Out Date: ****, 2017 Amendment #4 To: From: Contractors submitting a proposal for this project Brandon Mendiola, Palomar Health Project Information Project Name: Project Location: PMC East Emergency Department

More information

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements SECTION A CM INSTRUCTIONS TO BIDDERS SECTION B BID CATEGORY DESCRIPTIONS & BID FORMS BC-07: Building HVAC and Plumbing BC-08: Building Electric BC-09: General Trades BC-10: Masonry BC-11: Precast Structural

More information

KU West Campus LEEP II High Bay Facility Project # , A (c)

KU West Campus LEEP II High Bay Facility Project # , A (c) Number Revision Title Rev Date Discipline Bulletin Drawings B-West Structural Category S051 0 General Notes - Sheet 1 7/31/13 Structural Bid Package B- West Campus S052 0 General Notes - Sheet 2 7/31/13

More information

DIW Office and Lab Improvements - Phase 2, Project ID Date Issued: November 5, 2014

DIW Office and Lab Improvements - Phase 2, Project ID Date Issued: November 5, 2014 DIW Office and Lab Improvements - Phase 2, Project ID 102005 Date Issued: November 5, 201 ADDENDUM NO. This addendum will only be distributed via e-mail, but will remain available for viewing on the MSDGC

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies

More information

Summary of Modifications/Changes in this Update

Summary of Modifications/Changes in this Update Summary of Modifications/Changes in this Update This Summary of Changes is for information only. It is not a part of the referenced document, and should not be used for project documentation. U.S. Department

More information

Keith Kessler, VCA Buyer II

Keith Kessler, VCA Buyer II Department of Facilities and Transportation Services Design and Construction Services 8115 Gatehouse Road, Suite 3500 Falls Church, Virginia 22042-1203 January 30, 2017 ADDENDUM #02 TO ALL PROSPECTIVE

More information

Architectural precast Concrete EARTH FRIENDLY BLOCK

Architectural precast Concrete EARTH FRIENDLY BLOCK SECTION 03450a Architectural precast Concrete IRC 2006 EARTH FRIENDLY BLOCK PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Insulated concrete forms for: a. Exterior structural wall construction. b.

More information

ADDENDUM NO. ONE TO THE CONSTRUCTION DOCUMENTS September 19, 2017

ADDENDUM NO. ONE TO THE CONSTRUCTION DOCUMENTS September 19, 2017 General: ADDENDUM NO. ONE TO THE CONSTRUCTION DOCUMENTS September 19, 2017 The following changes, additions, or deletions shall be made to the following documents; all other conditions shall remain the

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information